Home » Departments & Services » Building Safety & Permits » Electrical Rough-in Most Frequent Violations-(Residential)
Final Frequent Electrical Violations - Residential
Current adopted edition of National Electrical Code-2008
- Ladder not provided for inspection of attic equipment - USBC 113.1.1
- Improper working space @ elec. panels and equip - 110.26
- Ground Fault requirements in kitchens, baths, garages, basement, outdoor, wet bar - 210.8
- Recepts. within 6’ of laundry sink must be GFCI protected - 210.8 (a)(7)
- Bath recept. outlets not separate 20 amp circuit - 210.11 (c) (3)
- Bath recept. outlet > than 36” from sink basin - 210.52 (d)
- Outdoor recept.outlet > than 6 1/2’ above grade - 210.52 (e)
- Recept. not located within 25’ of outdoor HVAC equip - 210.63
- Lights for interior stairs of 6 or more risers not switched at each level - 210.70 (a) (2) (c)
- Kitchen recept. located under countertop where overhang is > 6” beyond base - 210.52 (c) 5
- Kitchen countertop recept. spacing - 210.52 (c)
- Concrete encased electrodes (rebar) if present, must be used as grounding electrode - 250.50 & 250.52(3)
- Bonding means for other systems not provided ie: phone/TV - 250.94
- Grounding electrode conductor not secured to bldg surface - 250.64 (b)
- Insulated Equip. ground # 6 and smaller must have entire length finished green - 250.119
- Grounded (neutral) conductors not isolated at sub-panels in same bldg - 250.142(b)
- PVC conduit installed where subject to damage not schedule 80 - 300.5 (d)(4)
- Covers missing on outlet/junction boxes - 314.25
- Outlet boxes not flush with combustible surfaces - 410.116(2)
- Switches not grounded - 404.9 (b)
- Circuit breakers installed > 6’ 7” above floor - 404.8
- Receptacles not mounted rigid to surface - 406.4(b)
- Wet location recept. covers not weatherproof with cord cap inserted - 406.8 (B)
- Receptacle located in tub space - 406.8 (c)
- Panel not labeled specifically - 408.4 and P2720.1
- Ceiling fans, hanging fixtures located in 3’ x 8’ zone near tub/shower - 410.4 (d)
- Clothes closet light clearances - 410.10 (d)
- Cord length on appliances - 410.2
- Heat strip not identified on HVAC equip - 424.28
- Breaker lock/disconnect not provided for hard wired appliances ie: dishwasher, oven, water heater, etc. - 422.31(b)
- AC breaker/fuse size exceeds max. per label - 440.6
- Insufficient tub motor access - 680.73
- Tub motor not bonded to associated metal piping, etc. - P2720.1
- Sign not posted at service indicating optional generator system on site - 702.8
- Holes in exterior of house not sealed at elec. penetrations - IRC 703.1
- An intersystem bonding termination with capacity for at least three bonding conductors must be provided and connected to the service equipment grounding conductor or graounding electode system with a min. No. 6 Copper conductor - 250.94
- All 15 and 20 amp non-locking receptacles located in damp or wet locations must be listed WR Weather Resistant type - 406.8
- GFCIs for hydromassage tubs must be readily accessible" (not behind access panels under tubs) - 680.71